Description

The Cristal Controls CCRC Room Controller provides up to 4 control zones for standalone or centralized use. Capable of switching up to four 20A circuits, it offers the flexibility to control local or open areas.

Each zone can be individually controlled for dimming (0–10V) or on/off lighting zones. Easy to install, the CCRC controllers can be connected directly to the electrical conduit network without the need for a junction box. This powerful room controller offers the same features whether used locally or as part of a network.

Operation

The default functions enable dimming and ON/OFF control using a low-voltage switch or occupancy sensor. Each zone can be preprogrammed at the factory to execute custom scenes. In addition, CCRC room controllers offer a wide range of programmable functions and parameters. Using an RS-485 USB interface and the BACnet Browser software (free), users can adjust the maximum lighting level, button functions, occupancy delay, and more.

In a centralized networked system, all controllers can be modified by the building manager or through the Cristal Controls master management system, Jasper. With a scheduler, the CCRC room controller can easily be used to sweep ON and OFF an entire building. All parameters can be monitored and controlled remotely.

Features

  • Control up to 50x 0-10V fixtures per zone (sink or source type)
  • Maximum capacity of 20Amp per zone
  • Management of the contribution of natural brightness contribution by single or double zone
  • Specific light level adjustment according to the occupancy
  • Adjustable detection time by programming
  • Universal inputs for sensor and momentary low voltage switch
  • Timer and flick warning
  • Ability to record 16 preset scenes
  • Test Buttons for the Installer
  • HVAC system auxiliary contact
  • Native DALI and BACnetMSTP communication
  • UL508 / CSA assembly

Specifications

Case type Nema 1 Surface, lockable Screw Cover
Dimensions 12 ’’ (height) x 12 ’’ (length) x 4 ’’ (depth)
Inputs 120/240/277/347Vac
Relay output
Main 20A Rated Relay 120/277/347
CULus Vac / by zone
Secondary: 1A 24Vdc / Vac / per zone
Dimming output 0-10V sink or source (100mA)
Universal entry 3 (1x occupancy detector, 2x buttons) / per zone
Analog input 1 (1x light detector) / per zone
Native communication
BACnet MSTP (RS845)
DALI
Operating environment
(0C to 50C)
Certification
CSA and UL assembly