CC-WIXBEE GATEWAY
The CC-WiXBee gateway allows communication between the wireless nodes and the BACnet/IP network.
The CC-WiXBee gateway allows communication between the wireless nodes and the BACnet/IP network.
Ideal for outdoor lighting, with a plug conforming to ANSI C136.41 with 7 pins, it can support 0-10 VDC dimming.
Autonomous wireless communicating modules to control, monitor and measure lighting devices in real time. In addition, digital and analog inputs and outputs make it easy to create an intelligent, distributed system. No wires to pass. Significantly simplifies control and automation projects. Much more advanced and rational than control panels, cable networks and motion detectors connected to electrical circuits. Cristal wireless control technology adapts perfectly to complex automation situations for simple, fast and economical commissioning. Communication is in a wireless mesh network, at 2.4 GHz Radio Frequency, ISM (Industrial, Scientific and Medical) certified.
| Protocol | BACnet/IP |
| Supply | 12 VDC, 10 Watts |
| Operating temperature | 0°C to 70°C (32°F to 158°F) |
| Dimensions | 6.5″ X 6.5″ X 1″ |
| Outdoor antenna | 2.4 GHz (24″) 9dBi N-type (default) with 25 ″ cable coax 400 series (default) |
| Fixation | DIN rail mountable |
| Fixation | ANSI C136.41 with 7 pins |
| Supply | Même module pour tous les voltage de 110 à 480VAC (+/- 10%), 50 & 60Hz, Moins de 1 watts |
| Maximum charge | 7A max (7A @ 120-240Vac, 5A @ 277-347Vac and 2A @ 480VAC) |
| 0-10V dimming | For all types of power supply and 0-10V ballasts and requires to be "sink" (up to 200mA) or "source" (20mA) |
| Measurement of electrical aggregates | Amperage - Voltage - Power (2% margin of error), PF, operating hours counter. |
| 0-10V dimming | For all types of power supply and 0-10V ballasts and requires to be "sink" (up to 200mA) or "source" (20mA) |
| Standard entries | Digital input for motion sensor or switch (max: 30V) |
| Ouputs | 12V, max: 20 mA total |
| Ambient operating temperatures | -40 ° C to + 70 ° C |
| Relative humidity | Up to 99% non-condensing |
| Supply | L-N: 120, 277, 347 ou L-L: 208-240, 480V (tous les deux 50&60Hz) (Le voltage doit être spécifié), 2 watts |
| Maximum charge | 3 or 8 amps |
| Phase Angle Dimming | Continuous retroactive |
| Measurement of electrical aggregates | Amperage - Voltage - Power (2% margin of error), PF, operating hours counter. |
| Hi-Lo option | HID lighting control (with a magnetic ballast with double value capacitors). |
| Dimming 0-10V Standard | For all types of power supply and ballasts (Sink, up to 200mA) or (Source, 20mA live or more with external source) |
| Number of ballasts | 3 ballasts max |
| Standard entries | 3 digital (Motion sensor or switch (max: 48V)) + 2 analog inputs 0-10V |
| Ouputs | 2 digital (up to 48V- Max: 20mA total) |
| Ambient operating temperatures | -40 ° C to + 85 ° C |
| Relative humidity | Up to 100% non-condensing (option of perfectly waterproof case) |