[ Main Series ]

Description

The CC-PP1277 and CC-PP1347 power packs supply low voltage power to CRISTAL ceiling and wall-mounted occupancy sensors. They can switch lighting and HVAC loads based on a control signal received from the occupancy sensor.

The power packs employ a micro-controller that switches loads at a minimum voltage, protecting relay contacts from high inrush current common when switching electronic ballasts. This switching method reduces the stress across the relay contacts, preventing arc-over and assuring long reliable contact life. Similar to the power pack, the auxiliary relays do not supply power, but switch lighting and HVAC loads based on a control signal from the occupancy sensor.

The CC-PP1277 model employs a heavy-duty 20A relay, accepts 120V and 277V input and supplies up to 100mA at 24VDC. The CC-PP1347 model uses a 15A relay, accepts 347V input and and supplies up to 150mA at 24VDC.

Features

AC Power Input
CC-PP1277: 120/277 VAC
CC-PP1347: 347VAC
Output Voltage 24VDC
Output Current
CC-PP1277: 100mA
CC-PP1347: 150mA
Storage Temperature -20°F to 150°F (-29°C to 65° C)
Operating Temperature 32 to 104°F (0 to 40° C)
Maximum Humidity 90%
Standard
UL and cUL Listed
FCC (Class 2)
  • Single pole and normally open relay
  • Plenum rated
  • External colour coded leads for quick installation
  • Can be install inside or outside a standar 4 x 4-inch junction box
  • UL and cUL listed
  • Overcurrent protection
CC-PP1277
  • 100mA power output for 120 and 277VAC
  • 120/277VAC relay rated 15A for tungsten and 20A for ballast load
CC-PP1347
  • 150mA power output for 347VAC
  • 347VAC, 60Hz: 15A ballast 5200W

Applications

  • Business
  • Offices

Resources

Datasheet

Datasheet
English
616.21 kB
Datasheet
English
646.15 kB

Related Products