Description

The KC-601 interface is a Native BACnet application controller that communicates on a BACnet MS/TP RS-485 LAN. The controller is designed for lighting control applications in accordance with the KC-401 series controller. The KC-601 provide a complete relay panel control from 8 to 64 lighting control relays with parallel control devices as switches, motion detectors, BAS, etc.

  • Field Programmable KC-601 Controller
  • 4-Output RS-485 LAN @ 9600, 19200, 38400, 11520 bds
  • Support up to 4 Groups (KC-401) Configuration
  • A KC-601 can be networked with a KC-401 Relay Controller to control up to 64 relays and 4 groups
  • Multi-Group Relay Assignment Capability
  • Multiple Output Combinations (4 Devices):
    • KC-401 Sequencer Control Complying with photocell (Indoor and Outdoor) and 4 digital inputs
    • Inputs:
      • (1) RS-485 BACnet LAN Port
      • (1) RS-232 Port for PC
      • (1) Push-Button Reset
      • (1) BACnet Communication Status LED
      • (3) Programming Status LED Indicators
      • 24 Vac Supply
    • Outputs:
      • (4) RS-485 Communications Ports
      • (3) RS-485 Communication LED Indicators

Features

  • The KC-601 is a BACnet MS / TP device that allows the KC-401 sequencer to send and receive BACnet commands to and from a BAS.
  • It uses RS-485 networking technology under the native MS / TP BACnet protocol.
  • Building Management System (BAS) can configure and program from their database all of the functions inherent in the KC-601 BACnet node and KC-401 sequencer.
  • It conforms to BACnet native variables for lighting control.
  • It allows the programming, control and monitoring of up to 4 KC-401 sequencers controlling 16 relays each.
  • It allows the control and monitoring of 64 separate relays.
  • It allows the control and monitoring of 16 multi-contact devices such as switches, chronometers, volumetric detectors and lights.
Protocol – MS/TP BACnet
- Serial communication between KC-601 and KC-401
Supply 24 VAC, 125 mA, class 2
IEC Standards Compliance – IEC 60255-22-4 : Fast Transient Disturbance Tests
– IEC 61000-4-2 : Electrostatic Discharge Immunity Test
Environment - Temperature 0 ºC to 50 ºC (32 ºF to 122 ºF)
- Relative humidity 10 to 90% (without condensation)
Inputs - (1) RS-485 BACnet network port
- (1) RS-232 port for PC
- (1) Reset push button
- (1) BACnet Communication Status LED
- (3) LED indicators of programming status
Ouputs - (4) RS-485 communication ports
- (3) RS-485 Communication LED Indicators

Applications

  • The KC-601 provide a complete relay panel control from 8 to 64 lighting control relays with parallel control devices as switches, motion detectors, BAS, etc.