The KC-601 interface is a Native BACnet application controller that communicates on a BACnet MS/TP RS-485 LAN. The controller is designed for lighting control applications in accordance with the KC-401 series controller. The KC-601 provide a complete relay panel control from 8 to 64 lighting control relays with parallel control devices as switches, motion detectors, BAS, etc.

Description
- Field Programmable KC-601 Controller
- 4-Output RS-485 LAN @ 9600, 19200, 38400, 11520 bds
- Support up to 4 Groups (KC-401) Configuration
- A KC-601 can be networked with a KC-401 Relay Controller to control up to 64 relays and 4 groups
- Multi-Group Relay Assignment Capability
- Multiple Output Combinations (4 Devices):
- KC-401 Sequencer Control Complying with photocell (Indoor and Outdoor) and 4 digital inputs
- Inputs:
- (1) RS-485 BACnet LAN Port
- (1) RS-232 Port for PC
- (1) Push-Button Reset
- (1) BACnet Communication Status LED
- (3) Programming Status LED Indicators
- 24 Vac Supply
- Outputs:
- (4) RS-485 Communications Ports
- (3) RS-485 Communication LED Indicators
Features
- The KC-601 is a BACnet MS / TP device that allows the KC-401 sequencer to send and receive BACnet commands to and from a BAS.
- It uses RS-485 networking technology under the native MS / TP BACnet protocol.
- Building Management System (BAS) can configure and program from their database all of the functions inherent in the KC-601 BACnet node and KC-401 sequencer.
- It conforms to BACnet native variables for lighting control.
- It allows the programming, control and monitoring of up to 4 KC-401 sequencers controlling 16 relays each.
- It allows the control and monitoring of 64 separate relays.
- It allows the control and monitoring of 16 multi-contact devices such as switches, chronometers, volumetric detectors and lights.
Protocol | – MS/TP BACnet - Serial communication between KC-601 and KC-401 |
Supply | 24 VAC, 125 mA, class 2 |
IEC Standards Compliance | – IEC 60255-22-4 : Fast Transient Disturbance Tests – IEC 61000-4-2 : Electrostatic Discharge Immunity Test |
Environment | - Temperature 0 ºC to 50 ºC (32 ºF to 122 ºF) - Relative humidity 10 to 90% (without condensation) |
Inputs | - (1) RS-485 BACnet network port - (1) RS-232 port for PC - (1) Reset push button - (1) BACnet Communication Status LED - (3) LED indicators of programming status |
Ouputs | - (4) RS-485 communication ports - (3) RS-485 Communication LED Indicators |
Applications
- The KC-601 provide a complete relay panel control from 8 to 64 lighting control relays with parallel control devices as switches, motion detectors, BAS, etc.